GENERAL YORK Model BCH units are single package heat pump s designed for outdoor installation on a roof top or a slab. Supplemental electric heaters are available as field-installed accessories. The units are manufactured under ISO 9002 Quality System Certification.
035-12984-001-A-0204 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with national and local or municiple safety codes: Refer to T able 1 for Unit Application Data. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and / or the customer's expense.
size and type. Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in T able 3. CONDENSA TE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
035-12984-001-A-0204 Unitary Products Group 5 FIG . 3 - TYPICAL FIELD WIRING CONTROL WIRING POWER WIRING NOMINAL HEA TER SIZE KW VOL TAGE UNIT MODEL SIZE, NOMINAL TONS 45 MINIMUM SUPPL Y AIR CFM 7 10 .
heater accessory installation instruction for the heater electrical data. The minimum air flow limitations across these heaters are listed in T able 2. OPTIONAL ECONOMIZER RAIN HOOD The following procedure should be used when assembling an economizer rain hood onto a unit.
035-12984-001-A-0204 Unitary Products Group 7 FIG . 5 - ENTHALPY SET POINT ADJUSTMENT MODELS BCH 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd.,mm/in.) F AN MOTOR HP (Direct-Drive Units) F AN MOTOR HP (Belt-Drive Units) 305 x254 12 x 10 0.75 NA 305 x 254 12 x 10 NA 1.
035-12984-001-A-0204 8 Unitary Products Group FIGURE 6 - DIMENSIONS & CLEARANCES Front 610mm (24") Back 25mm (12") (Less Economizer) 914mm (36") (With Economizer) Left Side (Filter .
035-12984-001-A-0204 Unitary Products Group 9 DET AIL “B” UNIT WITH FIXED OUTDOOR AIR / BAROMETRIC RELIEF RAINHOOD 111 “ 260 “ 89 “ 210 A B 454 “ 184 “ 416 “ 260 “ 11 7 “ 1340 “ L.H. END VIEW REAR VIEW L.H. END VIEW REAR VIEW 638 “ 41 “ 698 267 “ 1 140 “ 502 “ “ CONDEN- SA TE DRAIN CONN.
035-12984-001-A-0204 10 Unitary Products Group T ABLE 4 - SUPPL Y AIR PERFORMANCE - BCH048 MODEL AIR FLOW m 3 /s / CFM Available External S tatic Pressure -Pa/ IWG* 223 / 0.90 248 / 1.00 273 / 1.10 298 / 1.20 322 / 1.30 347 / 1.40 372 / 1.50 RPM W atts RPM W atts RPM W atts RPM W atts RPM W atts RPM Watt s RPM Watt s 060 1.
035-12984-001-A-0204 Unitary Products Group 11 MODEL BCH POWER SUPPL Y VOL TAGE LIMIT ATIONS COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA TOT AL UNIT AMP ACITY , AMPS MAX. FUSE SIZE, (SEE NOTE 1) AMPS MAX. HACR BREAKER SIZE, AMPS MIN.
screw fully clockwise and then energize and de-energize terminals “R” to “G”. With terminals “R” to “G” energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained. 1 1. Replace the filter section access panel.
During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm ( in.) long, 1mm ( in.) apart and are mounted on a white base. See Figure 8. LOCKOUT CONTROL Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode: 1.
3. Using an inclined manometer , determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly , measuring the pressure drop across a wet coil under field conditions would be inaccurate. T o ensure a dry coil, the compressors should be de-energized while the test is being run.
035-12984-001-A-0204 Unitary Products Group 15.
Unitary Products Group 5005 Y ork Drive, Norman, Ok 73069 Subject to change without notice. Printed in U.S.A. Copyright by Y ork International Corporation 2004.
デバイスYork B3CH 048 and 060の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York B3CH 048 and 060をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork B3CH 048 and 060の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York B3CH 048 and 060の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York B3CH 048 and 060で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York B3CH 048 and 060を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork B3CH 048 and 060の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York B3CH 048 and 060に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork B3CH 048 and 060デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。