GENERAL These completely assembled indoor units include a well- insulated cabinet, a copper tube/aluminum fin coil, throw - away filters, a centrifugal blower , a blower motor , an adjust - able V -belt drive, a blower motor contactor and a small holding charge of an inert gas.
035-09651-001-A-0304 2 Unitary Products Group T ABLE OF CONTENTS GENERAL ............................................................................. 1 REFERENCE ............................................................................. 1 INSPECTION .
rate request for inspection by the carrier's agent should be made in writing. LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes.
035-09651-001-A-0304 4 Unitary Products Group FIG . 1 - UNIT SUSPENSION MOUNTING (Horizontal Application) Model Power Supply V oltage V ariation 1 Supply Air CFM Entering Air T emperatures, ° F Cooling - wb Heating - db Min. Max. Min. Max. Min. Max. Min.
WARNING: Do not permit overhanging structures or shrubs to obstruct air discharge. Additional height may be required for snow clearance if winter operation is expected.
Form 035-16650-001 – Supply Air Plenum Form 035-16621-001 – Return Air Grille Form 035-16632-001 – Base The supply air plenum and the return air grille should be used in lieu of ductwork only when a free blow/free return application is practical.
A 7/8" OD drain connection extends through right hand side of cabinet. Refer to Fig. 7 for recommended drain piping. The drain connection is located on the same side of the unit as the refrigerant connections. The line should be insulated where moisture drippage will be objectionable or cause damage to the area.
035-09651-001-A-0304 8 Unitary Products Group FIG . 9 - HOLE LOCA TIONS FOR PRESSURE DROP READINGS FIG . 10 - PRESSURE DROP ACROSS A DRY INDOOR COIL VS. SUPPL Y AIR CFM RPM CFM ESP 2 BHP KW ESP 2 BHP KW ESP 2 BHP KW ESP 2 BHP KW ESP 2 BHP KW F3EH090 (60 Hz) 2400 2700 3000 3300 3600 600 0.
035-09651-001-A-0304 Unitary Products Group 9 Model Accessory S tatic Resistance, IWG BLOWER CFM 2400 2700 3000 3300 3600 F3EH090 Electric Heat 10 KW 0.01 0.01 0.01 0.02 0.02 16 KW 0.01 0.02 0.02 0.03 0.04 26 KW 0.03 0.04 0.05 0.06 0.07 36 KW 0.05 0.07 0.
POWER AND CONTROL WIRING Install electrical wiring in accordance with the latest National Electrical Code (NFP A S tandard No. 70) and/or local regula - tions.
035-09651-001-A-0304 Unitary Products Group 11 FIG .12 - UNIT DIMENSIONS & CLEARANCES (F3EH090 & F4EH120) All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. ACCESSORIES • ELECTRIC HEA TER - Add 14-1/4" to unit height when used.
SECURE OWNER'S APPROV AL: When the system is functioning properly , secure the owner's approval. Show him the location of all disconnect switches and the thermostat.
デバイスYork F3EH090の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York F3EH090をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork F3EH090の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York F3EH090の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York F3EH090で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York F3EH090を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork F3EH090の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York F3EH090に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork F3EH090デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。